The Analog Input module uses 16 conseardive I/O points, beginning with the first I/O reference assigned to the I/O slot selected for the /nodule.

The table, it is assumed that the Analog Input module is placed in slot 3 of a properly configr.red 5 or 10-slot CPU rack (references 10 to 17 and 110 to 117).

These references are used for the example only, other valid references for I/O slots that allow 16 references can be used. The following table defines the use of each of the I/O points.

Number of Channels:- 4

Input Ranges :- +1 to +5 V dc or 4 to 20 mA

Resolution :- 8-bit binary (1 in 256)

Digital Outputs :- 8 bits, binary data output 4 bits, channel status

I/O Points Required :- 16 consecutive (per slot assignments for 16 points, 0 to 7 and 100 to 117, etc.)

LED Display (16 LEDs) :- 8 bits: Data being read into the selected channel 4 bits- Channel selected for Data Display 4 bits- Channels being scanned

Operating Temperature :- 0 to 60° C (32 to 140° F)

Relative Humidity :- 5% to 95% (non-condensing)

Input Impedance :- > 1 MΩ (Voltage put) 250 Ω (Current put)

Absolute Maximum ratings :- Voltage Input, 0 to +10 V dc,  Current Input, 0 to 30 mA

External Power Source :- +25 V dc, 65 inr.. (munimun,)

Accuracy vs. Temperature :- ±50 ppm (parts per.milimn) yer. 1°C

Accuracy :- ±1% at 25° C, maximum

GE Fanuc IC610MDL116B Analog Input Analog Module

The Analog Input module uses 16 conseardive I/O points, beginning with the first I/O reference assigned to the I/O slot selected for the /nodule.

The table, it is assumed that the Analog Input module is placed in slot 3 of a properly configr.red 5 or 10-slot CPU rack (references 10 to 17 and 110 to 117).

These references are used for the example only, other valid references for I/O slots that allow 16 references can be used. The following table defines the use of each of the I/O points.

Number of Channels:- 4

Input Ranges :- +1 to +5 V dc or 4 to 20 mA

Resolution :- 8-bit binary (1 in 256)

Digital Outputs :- 8 bits, binary data output 4 bits, channel status

I/O Points Required :- 16 consecutive (per slot assignments for 16 points, 0 to 7 and 100 to 117, etc.)

LED Display (16 LEDs) :- 8 bits: Data being read into the selected channel 4 bits- Channel selected for Data Display 4 bits- Channels being scanned

Operating Temperature :- 0 to 60° C (32 to 140° F)

Relative Humidity :- 5% to 95% (non-condensing)

Input Impedance :- > 1 MΩ (Voltage put) 250 Ω (Current put)

Absolute Maximum ratings :- Voltage Input, 0 to +10 V dc,  Current Input, 0 to 30 mA

External Power Source :- +25 V dc, 65 inr.. (munimun,)

Accuracy vs. Temperature :- ±50 ppm (parts per.milimn) yer. 1°C

Accuracy :- ±1% at 25° C, maximum